GSC3000Transmitter RemoteControl SystemsINSTALLATION & OPERATION MANUALIncludes Instructions for Lynx SoftwareVRC25005 SERIES

Strona 2 - Lynx Software version 5.0

UNPACKINGFor each item you ordered, please make sure that you have received all listed parts. If anything is missing, contactBurk Technology customer

Strona 3 - Contents

Running Macros as Timed EventsYou can configure macros to run on specific dates and/or times by setting them up as Timed Events in the UnitConfigurati

Strona 4

CREATING & EDITING MACROSYou can make your macros as simple or complex as you want. For a guide to all macro commands, operators andexpressions,

Strona 5

Abandoning Changes to a MacroIf you make changes to a macro that you do not wish to keep, click the Revert Macro icon. The Macro Editorwill resto

Strona 6

CHAPTER 10: MACROS95CUSTOMER SUPPORT: 978-486-3711 • [email protected] • www.burk.comSSoouurrccee CCooddee CCoommppoonneenntt DDeessccrriippttiioonn%

Strona 7

GSC3000 & VRC2500 INSTALLATION & OPERATION MANUALCHAPTER 10: MACROS96SSoouurrccee CCooddee CCoommppoonneenntt DDeessccrriippttiioonnME Can b

Strona 8

TYPES OF MACROSThe macro examples in this manual show line separations by the use of [CR]. When you see [CR] in theexamples, press enter to start a ne

Strona 9 - Introduction

CaptureMacros can take a capture to record unit conditions at any time during the macro sequence (see page 52 formore on captures). This could be use

Strona 10 - UNPACKING

WarningA warning message can be generated within a macro by using the word “WARNING” followed by the desired textwithin double quote (“ ”) marks (the

Strona 11 - Voice Interface Unit

While/WendThis statement is used to repeat a command or set of commands as long as a specific condition exists. Thestatement begins with the word “WHI

Strona 12 - COMPUTER REQUIREMENTS

MUTESTATEMETER/MUTESTATESTATUSThese commands check to see if the input channel selected is in a muted state. They do nothing to modify thestate. When

Strona 13 - SYSTEM OVERVIEW

GSC3000 I/O 8 & I/O 16 UnitVoice Interface Unit(GSC3000 only)CHAPTER 1: INTRODUCTION3CUSTOMER SUPPORT: 978-486-3711 • [email protected] • www.burk.

Strona 14 - Alarm Reporting

REMLOCThe REMLOC statement allows the I/O unit to return a value to indicate if it is in a REMOTE or LOCAL state.This equates to the front panel push

Strona 15 - Battery Backup

<< >>NOT EQUAL TO== EQUAL TO++ ADD–– SUBTRACT** MULTIPLY// DIVIDE%% –– Returns the INTEGER VALUE OF THE REMAINDER of a division pr

Strona 16 - CONTROLS & CONNECTORS

!! –– BOOLEAN NOT OPERATORThe “!” operator makes the statement following it the opposite of what it normally would have been.AANNDD –– BOOLEAN OPE

Strona 17

SSQQRR– SQUARE ROOTReturns the square root of X.YYEEAARRReturns the four-digit year in the current I/O unit.MMOONNTTHHReturns the decimal equivalent o

Strona 18 - GSC3000 I/O Unit

METERING MACROSMacros can be used to modify all parameters pertaining to the metering input channels, including the A/Dvalues, calibration constants,

Strona 19 - FFllaasshhiinngg RREEDD::

METERCCThe calibration constant of each metering channel is unique and may be modified manually or by a macro. Thecalibration constant is a multiplier

Strona 20

METEROFF/METERONThe METERON/METEROFF commands allow a macro to start or stop a metering channel from converting theanalog value into a digital value.

Strona 21 - Command Relay Unit

OR in an IF/THEN StatementExample 1 shows how a macro can examine a situation, thenchoose the appropriate course of action. The first line sets anindi

Strona 22

Start Transmitter This is an example of a macro that starts other macros after ashort time delay. The first line starts Macro #2. There is a 10-second

Strona 23 - Software & Site Setup

Self-Directed StartupThis example shows some more of the versatility of the macrolanguage. Here, a status channel triggered Macro #10 to run.The macro

Strona 24 - SETUP FUNCTIONS

Command Relay UnitWiring Interface UnitCOMPUTER REQUIREMENTSBefore installing the Lynx 5 software, verify that your computer meets the followingmmiinn

Strona 25 - Site Name

GSC3000 & VRC2500 INSTALLATION & OPERATION MANUAL112

Strona 26 - Primary Connection

When used with a GSC3000, the Voice Interface is an optional unit that provides dial-up telephone access toyour site. In a VRC2500, the Voice Interfac

Strona 27 - Site Sharing

3. If you are using a dial-up modem with the Voice Interface, disable auto-answer. With the recommendedU.S. Robotics modem, this is accomplished by se

Strona 28

ALARM REPORTINGCheck for AlarmsIf alarms are present when you first dial in to your site, the Voice Interface will connect to the first unit withalarm

Strona 29 - CONNECTION SETTINGS

METER & STATUS READINGSIn addition to alarm reporting, the Voice Interface can report status conditions and meter readings for theconnected unit.

Strona 30 - (GSC3000 ONLY)

The * or # key can be used more than once to adjust the output as desired (202***, for example). After thecommand has been issued, you can enter addit

Strona 31 - CONNECTING TO SITES

Using the Audio In ConnectorThe rear panel Audio In connector (1/8”, mono audio) sends audio from a connected device to the phone line.This is useful

Strona 32

CHAPTER 11: VOICE INTERFACE OPERATION119CUSTOMER SUPPORT: 978-486-3711 • [email protected] • www.burk.comVOICE INTERFACE CODE REFERENCEThe following is

Strona 33 - Lynx Software Overview

GSC3000 & VRC2500 INSTALLATION & OPERATION MANUAL120

Strona 34 - View Menu

The I/O and Voice Interface firmware for the GSC3000 and VRC2500 can be reloaded or updated using theLynx software and a direct connection to the unit

Strona 35 - Tools Menu

SYSTEM OVERVIEWGSC3000 Hardware ComponentsThe central component of a GSC3000 system is the I/O (input/output) unit, labeled I/O 8 or I/O 16depending o

Strona 36 - Site List: In Detail

5. Enter the File Name of the desired firmware version, or click the […] button to browse. By default,firmware files are stored in C:\Program Files\Bu

Strona 37 - Alarms List: In Detail

CLEARING UNIT MEMORYThe previous instructions allow you to clear firmware and unit memory so that you may load new firmware andreprogram the unit. If

Strona 38 - Captures Window: In Detail

GSC3000 & VRC2500 INSTALLATION & OPERATION MANUAL124

Strona 39 - STATUS BAR

GSC3000 I/O UNITDimensions:19” W x 10” D x 1.75” H (48.3cm W x 25.4cm D x 4.45cm H)Weight:9.1 lbs. (4.3 kg) – dryOperating Temperature:0 to 50°CPower

Strona 40

SSttaattuuss****::DB37; 16 binary (low/high) channels; input impedance >24kOhms; input voltage range -30 to 30VDCcontinuous; toggle threshold low-t

Strona 41 - I/O Unit Configuration

VRC2500Dimensions:19” W x 10.75” D x 3.5” H (48.3cm W x 27.3cm D x 8.9cm H); two rack units highWeight:11 lbs. (4.99 kg) – dryOperating Temperature:0

Strona 42 - Description

Interconnection Circuit:Standard toll-grade telephone circuit or dedicated two or four-wire interconnection with toll-grade performance;FCC Registered

Strona 43 - Metering

GSC3000 VOICE INTERFACEDimensions:19” W x 10” D x 1.75” H (48.3cm W x 25.4cm D x 4.45cm H)Weight:7 lbs. (3.2kg) – dryOperating Temperature:0 to 50°CPo

Strona 44 - FFiirrsstt LLoowweerr

WIRING INTERFACEDimensions:19” W x 1” D x 1.75” H (48.3cm W x 2.5cm D x 4.45cm H)Weight:1.2 lbs. (0.55kg) – dryRear Panel Connections:TTeerrmmiinnaall

Strona 45

FCC PART 15 COMPLIANCE STATEMENTThis equipment has been tested and found to comply with the limits for a Class A digital device, pursuant to Part15 of

Strona 46 - NNoonnee

MMooddeemmA modem connection uses a dial-up modem to connect to the remote unit. Modemconfiguration and installation instructions are in Chapter 6. NN

Strona 47 - Timed Events

GSC3000 & VRC2500 INSTALLATION & OPERATION MANUAL132

Strona 48 - CCaappttuurree

CUSTOMER SUPPORT: 978-486-3711 • [email protected] • www.burk.com133CAppendix C:Pinouts1 Command 1A2 Command 1B3 Command 2A4 Command 2B5 Command 3A6 Co

Strona 49 - Saving to an Archive

GSC3000 & VRC2500 INSTALLATION & OPERATION MANUALAPPENDIX C: PINOUTS1341 Metering 12 Metering 23 Metering 34 Metering 45 Metering 56 Metering

Strona 50 - CALIBRATION

CABLE PINOUTSDB9F-DB9F Null-Modem CableDB9F-DB25M Serial CableG-Bus Cable (GSC3000 only)G-Bus Terminator (GSC3000 only)APPENDIX C: PINOUTS135CUSTOMER

Strona 51 - Unit Properties Window

GSC3000 & VRC2500 INSTALLATION & OPERATION MANUAL136

Strona 52

CUSTOMER SUPPORT: 978-486-3711 • [email protected] • www.burk.com137DAppendix D:TroubleshootingSome problems experienced by GSC3000 and VRC2500 users a

Strona 53 - Configuration

GSC3000 & VRC2500 INSTALLATION & OPERATION MANUALAPPENDIX D: TROUBLESHOOTING138Lynx won't establish a direct / full-time connection to my

Strona 54

APPENDIX D: TROUBLESHOOTING139CUSTOMER SUPPORT: 978-486-3711 • [email protected] • www.burk.comMy dial-up modem connection isunreliable.One or both of

Strona 55 - VOICE SETUP

GSC3000 & VRC2500 INSTALLATION & OPERATION MANUALAPPENDIX D: TROUBLESHOOTING140I can't upload firmware to myGSC3000 I/O unit or I can&apo

Strona 56 - AFTER CONFIGURING YOUR UNIT

APPENDIX D: TROUBLESHOOTING141CUSTOMER SUPPORT: 978-486-3711 • [email protected] • www.burk.comThe Firmware Wizard reports anerror when I attempt to up

Strona 57 - Equipment Connections

Automatic FunctionsIn addition to remote monitoring and control, the GSC3000 and VRC2500 provide automatic control withmacros, actions and timed event

Strona 58 - Connection

Surge ProtectionAlthough the GSC3000 and VRC2500 have built-in resistance to voltage surges, we recommend that you use asurge protector or line condit

Strona 59

RReemmoottee//LLooccaall BBuuttttoonnThere are two modes of operation: REMOTE and LOCAL. REMOTE mode (indicatedby a solid green LED) is for standard

Strona 60

PPoowweerr CCoonnnneeccttoorrAccepts an AC voltage input range of 100-240VAC, 50/60Hz, 15W, without manualswitching.FFUULLLL--TTIIMMEEUsed to connect

Strona 61

PPoowweerr LLEEDDIndicates whether the unit is currently powered.RReemmoottee//LLooccaall LLEEDDThe REMOTE/LOCAL LED indicates whether the unit is i

Strona 62

GGSSCC33000000 && VVRRCC22550000 IInnssttaallllaattiioonn && OOppeerraattiioonn MMaannuuaall System Series 5Lynx Software versi

Strona 63

Voice Interface UnitThe Voice Interface unit is optional hardware for the GSC3000 that uses a standard telephone line to dial outand alert operators t

Strona 64 - CONNECTING A WIRING INTERFACE

CCOOMM11Standard RS-232 DB9 connector to use with the supplied null-modem cable.Connects to either a dial-up modem or your computer COM port for uploa

Strona 65

GSC3000 & VRC2500 INSTALLATION & OPERATION MANUAL14

Strona 66 - BEFORE LEAVING YOUR SITE

When you create a site in Lynx, you will specify primary and backup connection parameters, logging preferences,and other setup information. During ini

Strona 67

IMPORTANT! You must use the provided Lynx 5 CD key in order to activate the software. Although the Lynx 5 installerwill automatically detect your Lynx

Strona 68

Any time these instructions ask you to “select a site” or “select a unit,” go to the Site List and click on that siteor unit to highlight it.New SiteB

Strona 69 - Site Data & Reports

Time Zone1. Select the time zone where the site is located andenter the abbreviations for standard time anddaylight time. Indicate whether this site o

Strona 70 - Captures as Alarm Actions

RReemmoottee PPCC RRuunnnniinngg LLyynnxx..Your PC will access another computer on your LAN/WAN to get site data fromLynx. Enter the name of the Re

Strona 71 - USING THE REPORT WRITER

LoggingLynx can save site data directly to your computer andstore it in a database for use in reports. This is calledLogging, and it allows you to gen

Strona 72

5. Click Finish. The Site List will refresh to display the new site you added.6. If you have multiple sites, you can add the others now by once again

Strona 73 - Other Fields

CHAPTER 1: INTRODUCTION ...1Contacting B

Strona 74 - Printing Reports

3. When the Assign Unit Number dialog appears, select which PC COM port you areusing to connect to the I/O unit. Then enter the password for the unit

Strona 75 - IMPORT/EXPORT WIZARD

Once your units are networked, you may choose to connect your computer or modem to any one of them.Commands sent to the site will be directed to the a

Strona 76 - Export Configuration

GSC3000 & VRC2500 INSTALLATION & OPERATION MANUAL24

Strona 77 - USING THE CHARTING FUNCTION

Before working more with the software, it is a good idea to familiarize yourself with the menus and toolbars inthe Lynx main window. You have already

Strona 78

Clear Cache (page 43)Lynx stores unit configuration data in the cache so that it can be reloaded quickly when Lynx connects to theunit. For troublesho

Strona 79

Alarms (page 29)Displays all critical alarms at any connected site.Sites (page 28)The Site List displays icons for all of your sites, and the menu exp

Strona 80 - Channels

Sounds (page 85)Selects the sound files that Lynx will play for events. Options (page 85)This is where you customize the Lynx application settings to

Strona 81 - Custom View Editor

Event List: In DetailThe Event List is where Lynx logs activity related to each monitored site. Four categories of activities arerecorded, and you can

Strona 82 - Toolbar Icons

Macro Status: In DetailThe Macro Status window indicates which macros, if any, are currently running on the selected unit. The windowdisplays all the

Strona 83 - COMPONENT PROPERTIES

STATUS BAR The Status Bar on the bottom of the main Lynx window shows information about the current connection. Fromleft to right, the status bar disp

Strona 84 - Meter (Angular)

GSC3000 & VRC2500 INSTALLATION & OPERATION MANUALCONTENTSivConnect/Disconnect...

Strona 85 - Meter (linear)

GSC3000 & VRC2500 INSTALLATION & OPERATION MANUAL32

Strona 86 - Meter Display

The Unit Configuration menu is where you set up the metering, status and command functions for each unit.When an I/O unit is selected, you can configu

Strona 87 - STATUS COMPONENTS

The File menu and toolbar icons allow you to:Open archived configuration files (.set files)Save settings in an archive fileRestore the default configu

Strona 88 - Status Picture

Site DialingWhen connected to an external dial-up modem, I/O unitsfeature dial-out capability so that station personnel can benotified when a critical

Strona 89 - Command & LED

UUnniitt..Enter the unit of measurement (i.e. volts, watts, amps, etc.) used by this metering channel (up to fourcharacters). The Voice Interface is a

Strona 90 - OTHER COMPONENTS

FFiirrsstt UUppppeerrThe lower of the two upper limits. When the monitored value reaches the FirstUpper limit, the associated alarm/action is initiat

Strona 91

StatusThe Status tab is where you configure your status input channels. TTyyppee..In the main Status view, select Pull-Up or Pull-Downfor each channel

Strona 92 - SAVING CUSTOM VIEWS

CommandsSet up your command (output) channels from the Commands tab. MMooddee..Use the drop-down menu in the Mode field to selectwhether the output ty

Strona 93 - & Passwords

The standard Time view offers the flexibility to schedule typical activities. Click the Advanced button to scheduleevents on an even more precise sche

Strona 94 - Connectivity

Muting entries are executed in the order in which they are listed. If multiple entries for the same channel areentered, the desired result may not occ

Strona 95

CONTENTSCUSTOMER SUPPORT: 978-486-3711 • [email protected] • www.burk.comvSite Dialing...

Strona 96 - Warnings

Abandoning Changes / Restoring Default SettingsThere are two ways to abandon configuration changes:TToo aabbaannddoonn cchhaannggeess aanndd sstto

Strona 97 - CHANGING THE SITE PASSWORD

4. When you are finished calibrating the channels, click SSaavvee ttoo UUnniittto upload the new values to the I/Ounit. To abandon changes, click U

Strona 98 - LYNX USERS & PASSWORDS

GSC3000 & VRC2500 INSTALLATION & OPERATION MANUAL44

Strona 99 - VIEWING MACROS

The Voice Interface provides telephone dial-out capability for alarm reporting and dial-in touch-tone control.This feature is integrated on the VRC250

Strona 100 - THE MACRO EDITOR

If a dial-up modem is connected to the Voice Interface and you are using it to dial a computer, enter the phonenumber for the computer and ensure that

Strona 101 - CREATING & EDITING MACROS

USERSIn the Users tab, anyone with System privileges canestablish up to 32 unique Voice Interface users andpasswords and assign access levels for each

Strona 102 - MACRO SOURCE CODE

CCoommmmaanndd DDeellaayy..The command delay function can be set from 0 to 15 seconds to delay commands issued tothe site by DTMF tones. This functio

Strona 103

Now that your site is set up in Lynx and you have completed unit configuration, you are ready to connect yourmodems and site equipment to the system.

Strona 104

Burk Technology is able to offer only limited support for other modems used with GSC3000 or VRC2500. Ifyou are using an unsupported modem, please refe

Strona 105 - MACRO ME, ME, 5 [CR]

CHAPTER 6: MODEM & SITE EQUIPMENT CONNECTIONS51CUSTOMER SUPPORT: 978-486-3711 • [email protected] • www.burk.comConnecting a Dial-Up Modem to a GSC

Strona 106 - CAPTURE ME, 11 [CR]

GSC3000 & VRC2500 INSTALLATION & OPERATION MANUALCONTENTSviCustom View Settings...

Strona 107

FULL-TIME MODEM CONFIGURATION & CONNECTIONConfigurationProgram and configure your four-wire modems before you make connections to any equipment. B

Strona 108

CHAPTER 6: MODEM & SITE EQUIPMENT CONNECTIONS53CUSTOMER SUPPORT: 978-486-3711 • [email protected] • www.burk.com

Strona 109 - WHILE MUTESTATUSMETER(5)=1

GSC3000 & VRC2500 INSTALLATION & OPERATION MANUALCHAPTER 6: MODEM & SITE EQUIPMENT CONNECTIONS54ConnectionBe sure your modem is correctly

Strona 110 - MATHEMATICAL STATEMENTS

CHAPTER 6: MODEM & SITE EQUIPMENT CONNECTIONS55CUSTOMER SUPPORT: 978-486-3711 • [email protected] • www.burk.comConnecting a Full-Time Modem to a G

Strona 111

GSC3000 & VRC2500 INSTALLATION & OPERATION MANUALCHAPTER 6: MODEM & SITE EQUIPMENT CONNECTIONS56CONNECTING A WIRING INTERFACEThe Wiring In

Strona 112

CHAPTER 6: MODEM & SITE EQUIPMENT CONNECTIONS57CUSTOMER SUPPORT: 978-486-3711 • [email protected] • www.burk.comConnecting a Wiring Interface to a

Strona 113 - SQUARE ROOT

CONNECTING A COMMAND RELAY UNITThe Command Relay unit is used to provide isolation between the GSC3000 or VRC2500 unit and your siteequipment. The com

Strona 114 - WHILE METER(12)<100 [CR]

CHAPTER 6: MODEM & SITE EQUIPMENT CONNECTIONS59CUSTOMER SUPPORT: 978-486-3711 • [email protected] • www.burk.comConnecting a Command Relay to a GSC

Strona 115 - METERCC(14)=2.583 [CR]

GSC3000 & VRC2500 INSTALLATION & OPERATION MANUAL60

Strona 116 - METERON(15) [CR]

In addition to providing control and configuration functions, Lynx can also manage your site data and allow youto create customized reports for your s

Strona 117 - Example 2

Creating & Editing Macros...

Strona 118 - Macro #7

Taking CapturesSince captures can be used for a variety of purposes, there are a number of ways to set them up. To manuallytake a capture, just click

Strona 119 - Self-Directed Startup

If you have not enabled logging for this site, you can click the Save to Database button to manually save thecaptures to the Lynx database. Captures s

Strona 120

DateDDaattee RRaannggee.. Use the check boxes and drop down menus to specify the dates you would like included in thereport. The Include Most Recent

Strona 121 - Voice Interface Operation

Other FieldsIn addition to displaying data from status and metering channels, you can choose to include any of the followingin your report: AAppppllii

Strona 122 - Disconnecting

FooterThe Report Footer appears at the bottom of the last page in your report. You can include user-definedAAddddiittiioonnaall tteexxttin the Report

Strona 123 - ALARM REPORTING

SCHEDULING PRINT JOBSIn addition to manually printing reports from the Report Writer, you canschedule automatic print jobs. After you save your repor

Strona 124 - METER & STATUS READINGS

Export HistoryWhile the Report Writer allows you to save report data in textor HTML files, the Import/Export Wizard gives you the optionto save it in

Strona 125

Import ConfigurationOnce you have exported (saved) a Lynx configuration, youcan load it on another computer, or reload it on thiscomputer if you ever

Strona 126

GeneralTTiittllee..Enter a name for your chart. The name will appear in the View Listso you can easily identify it. When you save the chart, you can g

Strona 127 - Other Functions

X-AxisTTiittllee.. Choose a title for the X-axis (the horizontal row of values), orleave it blank. The X-axis always represents time. LLaabbeell CCo

Strona 128

GSC3000 & VRC2500 INSTALLATION & OPERATION MANUALviii

Strona 129 - Uploading Firmware

ChannelsUp to ten channels may be included in any graph. The more channelsyou use, the “busier” the chart will be. Keep in mind that the channelswill

Strona 130 - JP9 Jumper

With custom views, you can tailor the appearance of your site and channel data in the Lynx interface. TheCustom View Editor lets you place metering an

Strona 131 - CLEARING UNIT MEMORY

Tools in the Custom View EditorWith the Custom View Editor open, you will find the tools for creating your custom views in the menus at the topof the

Strona 132

You can customize the background color of the custom view screen by unchecking the Use Default box andclicking the browse button. You can select diffe

Strona 133 - Specifications & Warranty

General Properties & Click ActionsEvery component you add to the custom view has GGeenneerraall pprrooppeerrttiieessand CClliicckk AAccttiioonns

Strona 134 - Supplied Cables:

UUssee DDeeffaauulltt CCoolloorrss.. Check the box if you would like to use default colors for the meter background. Otherwise,leave it unchecked a

Strona 135

Meter DisplayRReevveerrssee SSccaallee..By default, meters start in the low end of the scale and run to the high end. Reverse scale resultsin the opp

Strona 136 - Interconnection Circuit:

FFoonntt//FFoonntt CCoolloorr.. Determines the font and font color used to show the meter values.SSppaacciinngg.. This sets how far from the meter

Strona 137 - GSC3000 VOICE INTERFACE

AArrrrooww SSttyyllee,, LLeennggtthh aanndd HHeeaadd SSiizzee..When configuring an arrow LED, you will also need to indicate the arrow style(orien

Strona 138 - COMMAND RELAY UNIT

CaptionAAuuttoommaattiiccaallllyy sseett OOnn//OOffff ccaappttiioonnss..Displays On/Off captions according to monitored condition. In the case of a

Strona 139 - WARRANTY

The GSC3000 and VRC2500 transmitter remote control systems are designed to streamline your remotefacilities management by providing a single interface

Strona 140

LLEEDD ppoossiittiioonn..Lets you choose where the LED appears on the command button.CommandWhen a click action is defined, any component can be used

Strona 141 - Appendix C:

UUssee TTrraannssppaarreennccyy MMaasskk.. Check the box if you want to select a color to show as transparent (the picturecomponent’s background co

Strona 142 - METERING

LabelThe Label component can be used to insert text anywhere in the custom view. As with all components, you canassign an action to the label or leave

Strona 143 - CABLE PINOUTS

A number of user-definable functions are available to help you customize your operation. Set up Sounds,Options, and Passwords to keep the application

Strona 144

GeneralDDiissaabbllee DDeeffaauulltt VViieewwss..If checked, Lynx will not showthe “default view” when a unit is selected in the sitelist. This opti

Strona 145 - Troubleshooting

MMaaxx SSiittee RReessppoonnssee TTiimmee.. When Lynx sends commands to a unit, it will allow up to the specified amount of timefor a response fro

Strona 146

If a connection is lost, Lynx can:•SShhooww tthhee LLiinnkk LLoossss NNoottiiffiiccaattiioonn DDiiaalloogg. •AAuuttoommaattiiccaallllyy ccllooss

Strona 147

SET TIMEThere are two options for setting the time at your sites. You can choose tosynchronize the time with your computer or to input the time manual

Strona 148

LYNX USERS & PASSWORDSIn addition to password protection for the remote control units, there are usernames and passwords used to access the Lynx a

Strona 149

Macros allow you to run detailed and complex command routines for a wide variety of tasks. Examples includeprocedures for restarting equipment after a